Ist ein externer FI-Schutzschalter vor dem go-e Charger in der Hausinstallation erforderlich?
The go-e Charger is equipped with an integrated DC protection module with DC detection and additional AC detection (6 mA DC, 20 mA AC).
On the building side, an RCD type A must be installed and a miniature circuit breaker must be installed upstream. The local installation regulations must be observed.
Miniature circuit breakers with characteristic B or C for 16 or 32 amperes are permissible:
• 3- or 4-pole for three-phase connection
• 2-pole for single-phase connection